- WANLIN evacuation software (V1.0) covers the full egress workflow: project and floor management, 2D/3D modelling of walkable space, doors and exits, stairs, ramps, escalators and elevators, occupant profiles and behaviours, checking, computation, 3D replay and statistics.
- Two compute modes ship in one engine: Steering for individual route choice and local avoidance, SFPE for hydraulic capacity analysis, plus a dual-mode comparison; the manual is explicit that results must state which mode produced them.
- Occupant modelling runs from profiles (speed distributions, body types, stairs and ramps behaviour) to placement tools and flow sources with schedules; behaviours chain waypoints, waits and assigned elevators.
- Smoke coupling is built in: static smoke zones, imported FDS results with real-time FED, and incapacitation states that colour the egress story.
- Outputs include cumulative evacuation curves, exit and door passage statistics, trajectory CSVs, room and measurement-zone reports, occupant contour maps, FED curves, image export and a standards check report.
- Replays are self-contained files that open on another computer - the demonstration format for client and committee briefings.
Two modelling philosophies sit behind every credible egress study. Steering resolves each person: route choice, local avoidance, queueing at doors, even assigned elevators. SFPE treats flow hydraulically: speed as a function of density, doors as capacity limiters. The WANLIN evacuation software runs either - or both side by side on the same model - so the reviewer can see how much of the answer is physics and how much is method.
The workflow: plan in, evidence out
- Build the space. Import a DXF drawing, image or OBJ reference, then draw rooms as rectangles or polygons, cut negative regions and holes, and place internal doors and final exits with widths, one-way flow and opening schedules.
- Connect the floors. Stairs, ramps, escalators, moving walkways and elevators join levels; stair width, speed behaviour and intermediate landings are modelled explicitly, and elevator dispatch can serve assigned occupants.
- Add the people. Occupant profiles set speed distributions, body types and stair behaviour; placement tools range from single points to room fills with proportional mixes, and flow sources can generate people on schedules.
- Give them purpose. Behaviours chain actions - waypoints, waits, assigned elevators, refuge rooms with safety conditions - and assisted teams with vehicles model staff-led evacuation of non-ambulant occupants.
- Check before you burn time. A pre-run check walks the navigation mesh and connectivity, and measurement zones stand ready for density and speed statistics.
- Run, replay, report. Compute, open the 3D result window, replay with cameras and animation, then export curves, tables and images.
Two engines, one model: Steering and SFPE
| Mode | What it resolves | Use it for |
|---|---|---|
| Steering | Individual route choice, predictive local avoidance, collision stops, door queueing and component permissions | Designs where behaviour matters: care homes, complex venues, staff-assisted evacuation |
| SFPE | Hydraulic capacity: speed-density relations, boundary layers, effective door widths, specific flow limits | Capacity checks for stairs, corridors and exits against flow assumptions |
| Dual mode | Both engines on the same model where the feature set allows | Sensitivity comparisons - how much of the answer is method, not physics |
The manual’s discipline applies to both: parameters such as time step and output interval should follow the analysis goal rather than “smallest possible”, and every reported number must state which mode produced it. Three clocks deserve care - simulation time, wall-clock compute time and replay playback time are different things, and conflating them is the classic review error.
Smoke coupling and FED exposure
Egress does not happen in clear air. The software accepts FDS smoke results and couples them to the evacuation: static smoke zones define hazard areas, imported FDS fields drive real-time FED (fractional effective dose) accumulation per occupant, and incapacitation states appear in the results - turning “evacuated in 240 seconds” into “evacuated before untenable, here is the margin”. Data sources and thresholds stay reviewable, which is what makes the tenability claim defensible.
The reports a reviewer expects
| Output | What it shows |
|---|---|
| Cumulative evacuation curve | Time versus people out; plateaus expose waits, congestion or sources not yet generated |
| Exit and door statistics | Usage counts and passage events per exit, internal door and stair segment, with flow windows that must stay consistent when compared |
| Trajectory CSV | Per-occupant time series for individual checking, merged or per-person |
| Room and zone reports | Occupancy histories, measurement-zone density and speed, source generation logs |
| Occupant contour maps | Density, queue and service-level maps with consistent rendering parameters between runs |
| FED and incapacitation | Per-occupant exposure curves and states where smoke data is coupled |
| Check report and images | A standards check report built from the model inputs, plus labelled plan and 3D screenshots |
For client meetings the deliverable is a self-contained replay file: geometry, trajectories and playback travel together, open on another computer, and show the committee exactly where the queue formed. The manual’s export advice doubles as review advice - label every exported image with software version, model name, compute mode, time range and occupant count.
Where it fits in fire engineering
Evacuation simulation sits between the fire model and the floor plan: the smoke model says when conditions degrade, the evacuation model says when people are out, and the design is adequate when the second number beats the first with margin. Typical applications include performance-based egress design for malls, schools, halls and care homes, stair and exit capacity studies, retrofit justification where code-prescribed widths cannot be met, and staff training where a 3D replay communicates faster than any table. To discuss a model for your building, contact 16710807777.
From this site: related products, news and FAQ
Simulation answers “what if”; hardware answers “what now”. The entries below are drawn live from this site’s own catalogue, newsroom and FAQ section - the detection and alarm devices that sit on the other side of the model.
Product line
- WANLIN-307 tamper proof smoke detector for Portugal Buyers: WANLIN-307 Standalone Smoke Al
- Battery powered wireless smoke detector for Japan Buyers: WANLIN-307 Standalone Smoke Alar
- Nursery smoke alarm for Portugal Buyers: WANLIN-307 Standalone Smoke Alarm Factory Direct
- Smoke detector sample order for Japan Buyers: WANLIN-307 Standalone Smoke Alarm Factory Di
Latest news
Key questions, answered
Steering and SFPE: which evacuation mode should be used?
They answer different questions. Steering resolves individuals - route choice, local avoidance, door queueing and assigned behaviour - and suits designs where behaviour matters, such as care homes or complex venues. SFPE computes flow hydraulically from speed-density relations and door capacity, and suits capacity checks. The software runs both on the same model, and the manual recommends stating which mode produced every reported number; some advanced actions or components are restricted to one mode.
What outputs does an evacuation study need?
At minimum: the cumulative evacuation curve (time versus people out), exit and door passage statistics with comparable time windows, occupant summaries and trajectory CSVs, and images or replay files labelled with software version, model name, mode, time range and occupant count. Where smoke data is coupled, FED histories and incapacitation states complete the tenability story. The manual warns against reading a truncated run as full evacuation and against comparing results with different sampling windows.
Scope disclosure: this page restates a software user manual (V1.0) in plain English for fire engineering audiences; it describes functionality as documented, not a certification or validation claim. Simulation results support engineering judgement - they do not replace project-specific parameter justification, numerical verification or professional review, and tutorial values are not design conditions. Support portal: xiaofangpinggu.com. For the full manual and licensing, contact wanlinfirecontrol@163.com or 16710807777.
What to watch
Watch for: FED-coupled egress studies moving from research to routine submittals, and reviewers asking which compute mode produced every curve.
Also on this site: the full topic guide hub, elderly fall detection monitor, fire service filing rules, and the site’s contact page for demos and licensing.